SUNWAY M XS 7500TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
100/
148
P093
Range
1000 ÷ 1100
1.0 ÷ 1.2
Instant
Undervoltage
Release Ratio
Default
1060
Level
ADVANCED
Address
693
Function
Sets the ratio between the trip threshold of the instant undervoltage fault
and the value at which the instant undervoltage fault is reset.
P094
Range
1 ÷ 1000
0.001 ÷ 1.000 s
Instant
Undervoltage
Trip Time
Default
5
Level
ADVANCED
Address
694
Function
Time during which the trip condition of the instant overvoltage must be
maintained to prompt the activation of the grid instant undervoltage fault.
P095
Range
1 ÷ 1000
0.001 ÷ 1.000 s
Instant
Undervoltage
Reset Time
Default
10
Level
ADVANCED
Address
695
Function
Time during which the trip condition of the instant overvoltage must be
maintained to prompt the reset of the grid instant undervoltage fault.
P096
Range
10 ÷ 300
[0.1 ÷ 3.00] Hz
Maximum
Frequency Trip
Threshold
Default
30 (Italy), 10 (Spain), 20 (Germany)
Level
ADVANCED
Address
696
Function
This parameter sets the maximum value of the frequency offset in respect
to the nominal value at which the grid maximum frequency fault trips.
P097
Range
995 ÷ 1100
0.995 ÷ 1.1
Maximum
Frequency
Release Ratio
Default
998
Level
ADVANCED
Address
697
Function
Sets the ratio between the trip frequency of the maximum frequency fault
and the value at which the maximum frequency fault is reset.
P098
Range
40 ÷ 1000
0.040 ÷ 1.000 s
Maximum
Frequency Trip
Time
Default
50 (Italy), 50 (Spain), 150 (Germany)
Level
ADVANCED
Address
698
Function
Time during which the trip condition of the maximum frequency must be
maintained to prompt the activation of the grid maximum frequency fault.