Release Date: 06/2022
TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
Page 27
1. Enter the 4-digit PIN to access the Supervisor Menu. PIN entry is made one digit at a time beginning with the leftmost digit.
Press
UP or DOWN
to scroll through the numbers 0 through 9.
2. When the correct number is displayed, press
ENTER
to select the digit. The cursor automatically moves to the next position.
If an error is made after pressing ENTER, press ESC to go back and change the digit.
NOTE: If the PIN is not correctly entered, the display returns to normal operation.
b. If the Supervisor PIN is not enabled, the Supervisor Menu selections display.
NOTE: See Enable, Disable, and Change the Supervisor PIN for more information about enabling the PIN.
3. Press
UP or DOWN
to scroll through the available menu selections. See Table 18 for a list of Supervisor Menu selections and their
descriptions.
NOTE: Each Supervisor Menu submenu has submenu selections in which you can access the configurable options.
NAVIGATING THE SUPERVISOR MENU
The Supervisor Menu is used to enable or disable probes and individual sensors, scan all sensors for status updates, and perform
diagnostics on alert conditions. It is also used to restore the device to a pre-installation state.
1. When the TDP05K Airflow Measuring System’s LCD screen displays the average temperature and average velocity or volume, press
MENU
and
UP or DOWN
until the arrow is next to the Supervisor Menu.
2. Press
ENTER
to access the Supervisor Menu settings.
a. If the Supervisor PIN is enabled, the LCD screen displays the following message:
Supervisor Menu Submenus
(Actual Display Name)
Description
Enable Supervisor PIN
(Enable Supv PIN)
When enabled, prevents unauthorized access to the Supervisor Menu.
Change Supervisor PIN
(Change Supv PIN)
Set or change the Supervisor Menu PIN.
Sensor Management
(Sensor Mgmt)
Scans the probe network for active and enabled sensors and enables or disables individual sensors. It
also displays the probe status and each sensor’s velocity and temperature reading.
Reset Sensors
(Reset Sensors)
Allows the cycle of power to the sensors.
Factory Default
(Factory Default)
Restores the device to the factory-default settings. Any previous settings made in the Operator and
Supervisor Menus are reset including dimensions, the Operator PIN, and custom text.
Exit Supervisor Menu
(Exit Supv Menu)
Returns the display to normal operation.
Table 18: Supervisor Menu Submenus