Release Date: 06/2022
TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
Page 17
Temperature Balance Configuration
The Temperature Balance Configuration submenu applies a temperature offset to the displayed and reported temperature and the
temperature used for analog outputs.
Selected Submenu
Submenu Selections
Submenu Selection Display
*Default values shown
Figure 12: Temperature Balance Flowchart
Temperature Balance
Configuration Submenu
Selections
Configurable Options
Temperature Balance Enable
Select On or Off.
Temperature Offset
Selection
Enter the currently selected value. The temperature displayed on the left side of line 2 is the offset
and the value on the right side of line 2 is a live view of the current temperature with the last
confirmed offset value. The offset range is ±5.4°F (±3°C).
Table 11: Temperature Balance Configuration Submenu Selections and Configurable Options
1. In the Operator Menu, press
UP or DOWN
to scroll to the Temperature Balance Configuration submenu.
2. Press
ENTER
.
3. Scroll through the submenu options and make any necessary updates. See Table 11 for a description of the Temperature Balance
Configuration submenu selection options and their configurable options.
UP
ENTER
ENTER
ENTER
ENTER
ESC or ENTER
ESC or ENTER
ESC
Return to
Operator Menu
UP
UP
DOWN
DOWN
DOWN