Release Date: 06/2022
TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
Page 11
Selecting Custom Text
1. Scroll to the
Line 2 Custom
submenu and press
ENTER
.
2. Press
UP or DOWN
to scroll through the available character set.
See Figure 5 for a list of available characters.
3. Press ENTER to choose a character when it is displayed. The
character is stored and the cursor advances one position to the
right. Press ESC to return to the previous character.
4. Fill the line with characters for the remaining positions. After the
seventh character is entered, the custom text is stored in memory
and the display returns to the Display Configuration submenu.
Analog Output 1 Parameters
The Analog Output 1 Parameters submenu is used to select the process
variables that Output 1 represents. Available process variables include
flow, none, setpoint, and temperature. If flow is selected, the output
represents the defined flow design range.
NOTE: The factory-default setting for Analog Output 1 is airflow velocity.
However, Output 1 or Output 2 can be configured for either airflow or
temperature.
Figure 5: Custom Text Character Chart
Figure 6: Analog Output 1 Parameters Flowchart
Selected Submenu
Submenu Selection Display
*Default values shown
Analog Output 1 Submenu Selection
Configurable Option
Output 1 Parameters
Select between flow, none, setpoint, and temperature.
Table 6: Analog Output 1 Submenu Selection and Configurable Option
1. In the Operator Menu, press
UP or DOWN
to scroll to the Analog Output 1 submenu.
2. Press
ENTER
.
3. Make any necessary updates to the submenu selection. See Table 6 for a description of the Analog Output 1 submenu selection
option and its configurable option.
Analog Output 2 Parameters
The Analog Output 2 Parameters menu allows you to select the process variables that Output 2 represents. Available process variables
include flow, temperature, none, and setpoint. If flow is selected, the output represents the defined flow design range. If temperature is
selected, the output span is your temperature design range. The temperature default is -25.6 to 120.2°F (-32°C to 49°C).
NOTE: The factory-default setting for Analog Output 2 is temperature.
Figure 7: Analog Output 2 Parameters Flowchart
Selected Submenu
Submenu Selection Display
*Default values shown
ENTER
ESC or ENTER
ENTER
ESC or ENTER