TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
Page 13
Selected Submenu
Submenu Selection Display
Flow Output LPF
The Flow Output LPF submenu allows you to select the level of process filtering applied to the flow outputs. The levels are 0 to 9, with 0
indicating the filter is off and 9 indicating maximum filtering. The filtering affects the reported flow values and analog channels configured
for flow. Display Filter is an additional filter selection applied only to the display.
NOTE: Each unit of filtering is equal to 10% filtering. For example, 2 is equal to 20%.
Figure 9: Flow Output LPF Flowchart
*Default values shown
Flow Output LPF Submenu Selection
Configurable Option
Flow LPF Selection
Select between 0 to 9 (9 equals 90% filtering)
Table 9: Flow Output LPF Submenu Selection and Configurable Option
1. In the Operator Menu, press
UP or DOWN
to scroll to the Flow Output LPF submenu.
2. Press
ENTER
.
3. Make any necessary updates to the submenu selection. See Table 9 for a description of the Flow Output LPF submenu selection
option and its configurable option.
ENTER
ESC or ENTER