TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
Release Date: 06/2022
Page 18
K-Factor Configuration
The K-Factor Configuration submenu turns K-Factor on and calculates a K-Factor gain and offset from measured and reference data. The
K-Factor gain and offset values can also be manually configured.
NOTE: The auto K-Factor feature only works in FPM at this time..
Selected Submenu
Submenu Selections
Submenu Selection Display
*Default values shown
Figure 13: K-Factor Configuration Flowchart
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESC or ENTER
ESC
ESC
ESC
ESC
ESC
3 Seconds
ESC
3 Seconds
ESC
3 Seconds
ESC
Returns to Operator Menu
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
NOTE:
1. Only when calculate K-Factor is set to No.
2. Only when calculate K-Factor is set to Yes
3. Only when #of Data Points set to 1 or higher
4. Only when #of Data Points is set to 2 or higher
5. Only when #of Data Points is set to 3
Calculate K-Factor?
K-Factor Gain
1
K-Factor Offset
1
Number of Data Points
2
System at Point 1
2.3
Point 1 Velocity
2.3
Pt 1 Velocity
→
System @ Pt 2
2,4
?
System @ Pt 2
→
Pt 2
2,4
Velocity
System at Point 3
2.5
Point 3 Velocity
2.5
Exit this Menu
Generate K-Factor
2