TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
Page 23
BACnet Network Configuration
The BACnet Network Configuration submenu turns BACnet on or off and configures parameters based on the BACnet type.
Selected Submenu
Submenu Selections
Submenu Selection Display
Figure 15: BACnet Configuration Flowchart
BACnet Network
Configuration Submenu
Selections
Configurable Options
BACnet On/Off
Select On or Off.
BACnet Instance
Update the currently selected value. The instance number must be unique from all BACnet devices on
the entire system. The range of values is 1 to 4,194,302.
BACnet Address
Select a value between 4 and 127. Holding down the button increases the rate the value updates.
BACnet Max Mast
Select a value between 1 and 127. Holding down the button increases the rate the value updates.
BACnet Baud Rate
Select the 9,600, 19,200, 38,400 (default), or 76,800 baud rate.
Table 14: BACnet Network Configuration Submenu Selections and Configurable Options
1. In the Operator Menu, press
UP or DOWN
to scroll to the BACnet Network Configuration submenu.
2. Press
ENTER
.
3. Scroll through the submenu options and make any necessary updates. See Table 14 for a description of the BACnet Network
Configuration submenu selection options and their configurable options.
Firmware Note:
Only
ONE
Network output configuration can be active at a time.
- Modbus RTU (Default On)
- BACnet (Default Off)