TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
Release Date: 06/2022
Page 24
Modbus RTU Network Configuration
The Modbus RTU Network Configuration sub-menu turns Modbus RTU on or off and configures parameters based on the Modbus RTU
type.
Selected Submenu
Submenu Selections
Submenu Selection Display
Figure 16: Modbus RTU Network Configuration Flowchart
Modbus RTU Network
Configuration Submenu
Selections
Configurable Options
Modbus On/Off
Select On or Off.
Modbus Address
Select a value between 1 and 247. Holding down the button increases the rate the value updates.
Modbus Baud Rate
Select baud rate of 9600, 19200, 38400 (default), 57600, 76800, or 115200.
Modbus Parity
Select ODD, EVEN (default), NONE1 (one stop bit), or NONE2 (two stop bits).
Float Order
Select Little Endian (default) or Big Endian.
String Order
Select Normal (default) or Swapped.
Table 15: Modbus RTU Network Configuration Submenu Selections and Configurable Options
Firmware Note:
Only
ONE
Network output configuration can be active at a time.
- Modbus RTU (Default On)
- BACnet (Default Off)