Release Date: 06/2022
TDP05K Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
Page 19
4. Press
UP or DOWN
to change the setting and
ENTER
to confirm the setting. The new setting is stored in memory and the display
returns to the K-Factor Configuration submenu.
5. Press
UP or DOWN
to scroll to the
Calculate K-Factor
submenu selection and press
ENTER
.
6. Press
UP and DOWN
to scroll between Yes or No. Press
ENTER
to make a selection. If No is selected, see Automatic Calculation of
K-Factor Not Enabled. If Yes is selected, see Automatic Calculation of K-Factor Enabled.
3. Press
ENTER
. The display indicates the current K-Factor setting (Off or On).
2. Press
ENTER
to view the K-Factor Configuration submenu. Scroll to the
K-Factor Enable
? submenu selection.
1. This submenu selection only appears when Calculate K-Factor is set to No.
2. This submenu selection only appears when Calculate K-Factor is set to Yes.
K-Factor Configuration Submenu
Selections
Configuration Options
K-Factor Enable?
Select On or Off.
Calculate K-Factor
Select between Yes or No.
Manual Gain
1
Update the currently selected value.
Manual Offset
1
Update the currently selected value.
Number of Data Points
2
Select between one to three points for calculating the K-Factor.
System at Point 1
2
Record the current velocity over the sensors as reference point 1.
Point 1 Velocity
2
Update the currently selected value. Reference point 1 is displayed on the right side and the
measured value is entered on the left.
System at Point 2
2
Record the current velocity over the sensors as reference point 2.
Point 2 Velocity
2
Update the currently selected value. Reference point 2 is displayed on the right side and the
measured value is entered on the left.
System at Point 3
2
Record the current velocity over the sensors as reference point 3.
Point 3 Velocity
2
Update the currently selected value. Reference point 3 is displayed on the right side and the
measured value is entered on the left.
Generate K-Factor
2
Calculate and update the K-Factor values used then display the calculated values.
Table 12: K-Factor Configuration Submenu Selections and Configurable Options
Configuring the K-Factor
1. In the Operator Menu, press
UP or DOWN
to scroll to the
K-Factor Configuration
submenu.