3.7.1.6
Versions -XX-YF
3.7.1.6.1 1-wire with spring return with configurable spring return period
24...240 VAC/DC
~
~
–
+
PE
1
2
3
4
PA
5
Spring return in ~ 10 s = default connection
Spring return in ~ 3 s = additional bridge to terminal 5
For 1-wire control, the heating
is not active if contact is
broken.
Caution!
Fig.
28: SB2.1 - cable type 5+PE, cable diameter 7.5
mm
3.7.1.6.2 1-wire with spring return with configurable spring return period
continuous
Self-adaptation:
Inverse operation:
24...240 VAC/DC
~
~
–
+
PE
1
2
3
4
PA
1
2
3
4
5
6
YmA YVDC
T
VDC/mAUmA UVDC
5
Spring return in ~ 10 s = default connection
Spring return in ~ 3 s = additional bridge to
terminal 5
Runtime option for spring-return drives:
Bridge 3 – 4 inverts
the input and
feedback signals
Automatic alignment of positioning signal
and feedback signal with regard to the
angle of rotation (or travel) is done by
pressing the button (T) for at least 3 s.
Fig.
29: SB5.1 - cable type 5+PE, cable diameter 7.5
mm / cable type 6, cable diameter
7.4
mm
3 | Device description
32
Translation of the original installation guide · Version 1.0 · 2021-05-27