Electrical connection options
3-point with spring return constant
1-wire with spring return constant
Cable type 6, cable diameter 7.4
mm
1-wire with spring return with con-
figurable spring return period con-
tinuous [p.22]
1-wire with spring return with con-
stant spring return period continuous
[p.22]
1-wire with spring return continu-
ous without feedback signal [p.23]
3-point with spring return with con-
figurable spring return period con-
tinuous feedback signal [p.23]
3-point with spring return with con-
figurable spring return period con-
tinuous [p.24]
3-point with spring return constant
spring return period continuous [p.25]
Electrical characteristics limit switch
min.
typ.
max.
unit
Switch point CLOSED
Switch point OPENED
-2
-2
5
85
+2
+2
°
°
Signal operation
• U
max
DC*
• I
max
DC*
• I
min
AC/DC*
48
1
5
V
A
mA
Power operation
• U
max
AC*
• U
min
AC/DC*
• I
max
AC*
250
5
5
V
V
A
After one-off operation
with U > 24
VAC/DC or I > 100
mA:
• U
min
AC/DC*
• I
min
AC/DC*
12
100
V
mA
3 | Device description
178
Translation of the original installation guide · Version 1.0 · 2021-05-27