Electrical characteristics
min.
typ.
max.
unit
Minimum nominal voltage (at room temperature)
–10
%
24
+10
% VAC/DC
Maximum nominal voltage (at room temperature)
–10
%
240
+10
% VAC/DC
Minimum mains frequency
–20
%
50
+20
%
Hz
Maximum mains frequency
-20
%
60
+20
%
Hz
Nominal current (at room temperature)
Power consumption as a function of
Power consumption standby*
5
W
Power consumption heating mode*
16
W
Power consumption in operation
Power consumption as a function of
Switch-on peak
• at 24
VDC (for approx. 2 seconds)*
• at 240
VDC (for approx. 2 seconds)*
2
2
A
A
Maximum duty cycle for motor run time*
3
s
15
s, 30
s, 60
s, 120
s
60 s enforced pause after 3
s motor operation
100
%
Electrical connection options
Cable type 9+PE, cable diameter 8.8
mm
1-wire with spring return constant
spring return period BF1/BF3 [p.42]
Electrical characteristics limit switch
min.
typ.
max.
unit
Switch point CLOSED
Switch point OPEN
-2
-2
5
85
+2
+2
°
°
Signal operation
• U
max
DC*
• I
max
DC*
• I
min
AC/DC*
48
1
5
V
A
mA
Power operation
• U
max
AC*
• U
min
AC/DC*
• I
max
AC*
250
5
5
V
V
A
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27