Electrical characteristics
min.
typ.
max.
unit
Maximum duty cycle for motor run time*
40
s, 60
s, 90
s, 120
s, 150
s
100
%
Electrical connection options
Cable type 4+PE, cable diameter 7.2
mm
3-point no spring return [p.18]
3-point with spring return constant
1-wire with spring return constant
Cable type 6, cable diameter 7.4
mm
Integrated limit switch [p.20]
Electrical characteristics limit switch
min.
typ.
max.
unit
Switch point CLOSED
Switch point OPENED
-2
-2
5
85
+2
+2
°
°
Signal operation
• U
max
DC*
• I
max
DC*
• I
min
AC/DC*
48
1
5
V
A
mA
Power operation
• U
max
AC*
• U
min
AC/DC*
• I
max
AC*
250
5
5
V
V
A
After one-off operation
with U > 24
VAC/DC or I > 100
mA:
• U
min
AC/DC*
• I
min
AC/DC*
12
100
V
mA
Environmental conditions
min.
typ.
max.
unit
Humidity (not condensing)
90
% rH
Protection class as per DIN EN 60529
IP67
Operation
• Ambient temperature (T6)
• Ambient temperature (T5)
–40
–40
+40
+50
°C
°C
Storage
• Ambient temperature
-40
+70
°C
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27
171