Electrical characteristics limit switch
min.
typ.
max.
unit
After one-off operation
with U > 24
VAC/DC or I > 100
mA:
• U
min
AC/DC*
• I
min
AC/DC*
12
100
V
mA
Environmental conditions
min.
typ.
max.
unit
Humidity (not condensing)
90
% rH
Protection class as per DIN EN 60529
IP66
Operation
• Ambient temperature (T6)
• Ambient temperature (T5)
–40
–40
+40
+50
°C
°C
Storage
• Ambient temperature
–40
+70
°C
*: Nominal value: please note that nominal values are also subject to tolerances. For more
detailed information, see:
3.10.29 Max-30-BF, Max-30-BF-CTM
Mechanical characteristics
min.
typ.
max.
unit
Motor torque*
30
Nm
Motor run time for 90° (can be configured with rotary switch)*
40
60
90
120
150
s
Spring torque*
30
Nm
Spring return period for 90°*
20
s
Minimum angle of rotation*
-5
°
Maximum angle of rotation*
90
°
Weight*
• Max-30-BF
• Max-30-BF-CTM
9.5
9.5
kg
kg
3 | Device description
126