3.7.1.5.2 1-wire with spring return continuous activation
Self-adaptation:
24 VAC/DC
~
~
–
+
PE
1
2
PA
3
4
5
Y
mA
T
GND
U
VDC
Automatic alignment of positioning signal
and feedback signal with regard to the
angle of rotation (or travel) is done by
pressing the button (T) for at least 3 s.
Fig.
24: SB6.1 - cable type 5+PE, cable diameter 7.5
mm
3.7.1.5.3 3-point with spring return with configurable spring return period
24...240 VAC/DC
~
~
–
+
PE
a
b
1
2
3
4
PA
5
Spring return in ~ 10 s = default connection
Spring return in ~ 3 s = additional bridge to terminal 5
Fig.
25: SB2.0 - cable type 5+PE, cable diameter 7.5
mm
3 | Device description
30
Translation of the original installation guide · Version 1.0 · 2021-05-27