Electrical characteristics
min.
typ.
max.
unit
Nominal current (at room temperature)
Power consumption standby*
5
W
Power consumption heating mode*
16
W
Power consumption in operation
Switch-on peak
• at 24
VDC (for approx. 2 seconds)*
• at 240
VDC (for approx. 2 seconds)*
2
2
A
A
Maximum duty cycle for motor run time*
40
s, 60
s, 90
s, 120
s, 150
s
100
%
Electrical connection options
Cable type 3+PE, cable diameter 6.0
mm
1-wire with spring return constant
spring return period F3 [p.53]
2-wire with spring return constant
spring-return period F3 [p.54]
Environmental conditions
min.
typ.
max.
unit
Humidity (not condensing)
90
% rH
Protection class as per DIN EN 60529
IP67
Operation
• Ambient temperature (T6)
• Ambient temperature (T5)
–40
–40
+40
+50
°C
°C
Storage
• Ambient temperature
-40
+70
°C
*: Nominal value: please note that nominal values are also subject to tolerances. For more
detailed information, see:
3.10.40 Max-50-SF, Max-50-SF-CTM, Max-50-SF-VAM
Mechanical characteristics
min.
typ.
max.
unit
Motor torque*
50
Nm
Motor run time for 90° (can be configured with rotary switch)*
40
60
90
120
150
s
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27
151