Dimensions
min.
typ.
max.
unit
Max-5.10-YF-VAS
L
W
H
–1
–1
–1
211
96
81
+1
+1
+1
mm
mm
mm
Hollow shaft double square
12
×
12
mm
Allen key provided for manual adjustment in accordance with
these instructions*
3
mm
Electrical characteristics
min.
typ.
max.
unit
Minimum nominal voltage (at room temperature)
–10
%
24
+10
% VAC/DC
Maximum nominal voltage (at room temperature)
–10
%
240
+10
% VAC/DC
Minimum mains frequency
–20
%
50
+20
%
Hz
Maximum mains frequency
–20
%
60
+20
%
Hz
Nominal current (at room temperature)
Power consumption as a function of
Power consumption standby*
5
W
Power consumption heating mode*
16
W
Power consumption in operation
Power consumption as a function of
Switch-on peak
• at 24
VDC (for approx. 2 seconds)*
• at 240
VDC (for approx. 2 seconds)*
2
2
A
A
Maximum duty cycle for motor run time
7.5
s, 15
s, 30
s, 60
s, 120
s
100
%
Electrical connection options
Cable type 5+PE, cable diameter 7.5
mm
1-wire with spring return with con-
figurable spring return period [p.26]
3-point with spring return with con-
figurable spring return period [p.26]
1-wire with spring return continu-
Without spring return continuous
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27
73