Reference Manual
00809-0100-4803, Rev GA
Installation
September 2017
Installation
3.3
Installation considerations
3.3.1
General
Measurement performance depends upon proper installation of the transmitter, impulse piping, and
process temperature sensor. Mount the transmitter close to the process and use minimum piping to
achieve best performance. Also, consider the need for easy access, personnel safety, practical field
calibration, and a suitable transmitter environment. Install the transmitter to minimize vibration, shock,
and temperature fluctuation.
Note
Install the enclosed pipe plug (found in the box) in the unused conduit opening if optional process
temperature input is not used. For proper straight and tapered thread engagement requirements, see
the appropriate approvals drawings in
Appendix B: Product Certifications
For material compatibility considerations, see Material Selection
3.3.2
Mechanical
For steam service or for applications with process temperatures greater than the limits of the
transmitter, do not blow down impulse piping through the transmitter. Flush lines with the blocking
valves closed and refill lines with water before resuming measurement.
When the transmitter is mounted on its side, position the coplanar flange to ensure proper venting or
draining. Mount the flange as shown in
, keeping drain/vent connections on the
bottom for gas service and on the top for liquid service.
3.3.3
Environmental
“Cover installation” on page 69
can help optimize transmitter performance.
Mount the transmitter to minimize ambient temperature changes, vibration, mechanical shock, and to
avoid external contact with corrosive materials.
“Specifications and Reference Data” on page 125
temperature operating limits.
3.4
Installation procedures
3.4.1
Configure security (write protect)
Changes to the transmitter configuration data can be prevented with the security (write protect) switch
located on the feature board. See
for the location of the switch. Position the
switch in the
ON
position to prevent accidental or deliberate change of configuration data.
If the transmitter write protection switch is in the
ON
position, the transmitter will not accept any
“writes” to its memory. Configuration changes, such as digital trim and reranging, cannot take place
when the transmitter security is on.
To reposition the switches, follow the procedure described below:
1. Do not remove the transmitter covers in explosive atmospheres when the circuit is live. If the
transmitter is live, set the loop to manual and remove power.
2. Remove the housing cover opposite the field terminal side of the housing.
3. To reposition the switches as desired, slide the security and alarm switches into the preferred position
using a small screwdriver. See
.
Содержание 3051S Series
Страница 1: ...Reference Manual 00809 0100 4803 Rev GA September 2017 Rosemount 3051S MultiVariable Transmitter ...
Страница 2: ......
Страница 114: ...106 Reference Manual 00809 0100 4803 Rev GA Operation and Maintenance September 2017 Operation and Maintenance ...
Страница 126: ...118 Reference Manual 00809 0100 4803 Rev GA Troubleshooting September 2017 Troubleshooting ...
Страница 171: ...Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA 163 Product Certifications ...
Страница 173: ...Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA 165 Product Certifications ...
Страница 176: ...168 Product Certifications Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA ...
Страница 180: ...172 Product Certifications Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA CO S CO O ...
Страница 181: ...Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA 173 Product Certifications ...
Страница 182: ...174 Product Certifications Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA ...
Страница 184: ...176 Product Certifications Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA ...
Страница 185: ...Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA 177 Product Certifications ...
Страница 187: ...Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA 179 Product Certifications ...
Страница 188: ...180 Product Certifications Product Certifications September 2017 Reference Manual 00809 0100 4803 Rev GA ...
Страница 189: ......