Double Sheet Control System R1000 series L20
with integrated fieldbus interface
B0063191 / 1.3
Start-up
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
85
System parameter 4:
Selecting the dimensions for output via fieldbus (mm / inch).
Fig. 64: Selecting the dimensions for the fieldbus output
The multiplication factor of the output is determined by the type of sensors being used.
Sensor types
Multiplication factor (at inch resp. mm)
LAAS10, ,
LAAS40 and
0,0001 inch or 0,001mm
LAAS200 and
0,001 inch or 0,01mm
LAAS10, , LAAS200, are in preparation
System parameter 5:
Setting the display time
Fig. 65: Setting the display time
The maximal measured values (peak values) for the specified time are displayed here(holding
time). This time is for the display only. Values between 0.0 seconds and 2.0 seconds can be set.
System parameter 6:
Setting the bus address.
Fig. 66: Setting the fieldbus address
•
Profibus:
1 - 125
•
DeviceNet: 0 - 63
•
CanOpen:
1 - 127
•
ProfiNet IO: ---
•
CC-Link:
1 – 63
• EtherNet/IP:
---
• EtherCAT: ---
system parameter: 4
bus readout value in
mm
*0.001 (LAAS10/..40)
system parameter: 5
display time
2.0 s
system parameter: 6
bus address
1