6.6.3 EDS file for CanOpen
The EDS file contains the specific configuration data of the slaves. The data must be known to the
master.
The manufacturers of the master supply the tools for the integration of the EDS file into the
network. Roland Electronic does not supply such tools, because they have to be compatible with
the interface design of the master.
The EDS file is supplied on a CD or can be downloaded from the Roland homepage.
Note
3 PDOs with 8 Bytes each are set.
By pressing the key “
▼
” status indicators are shown on the display.
Status Indicators
Nr.
LED
State
Description
LED 1 STATUS Off
Normal operation
Red
Unrecoverable fault detected
LED 2 RUN
Off
Module not powered
Green
Module is in the OPERATIONAL state
Green, single flash
Module is in the STOPPED state
Green, blinking
Module is in the PRE-OPERATIONAL state
Red, blinking
Bus initialisation fault
LED 3 ERROR
Off
No error
Red Bus
off
Red, single flash
Warning limit reached
Red, double flash
Error Control Event
Red, triple flash
Sync Error
LED 4 POWER Off
Module not powered
Green Module
powered