Installation Manual
40
Location: 060 System Control 2
Default: 11
The location contains two digits:
•
First digit
: Determines the digit corresponding to the choices involving 3-
minute bypass / IMQ Installation bit / Czech installation bit / UL installation bit.
•
Second digit
: Determines the digit corresponding to the use of Auto arming
Pre-Warning / Alarm restore.
Comments on System Control 2 (Location 060: 1
st
Digit)
3 Minute Bypass IMQ Installation
Czech installation UL installation
Yes
: All zones will
be automatically
bypassed for 3
minutes when
power is restored
to an “unpowered”
system. This
prevents potential
false alarms by
allowing time for
the stabilization of
motion and/or
smoke detectors.
No
: No bypassing
occurs.
Yes
: Causes the following
parameters to function as
follows:
•
An open zone during Auto
Arming will activate an
alarm and the system will
not be armed.
•
UO Arm Follow (Pulsed or
Latched). UO will be
activated immediately,
regardless of the Exit
Delay time.
•
AC loss report and UO
follow AC loss are
activated after a delay of
30 minutes.
No
:
•
Auto Arming – An open
zone during auto-arming
will be bypassed and the
system will be armed.
•
UO arm follow (Pulsed or
Latched). UO will be
activated after the Exit
Delay time.
•
AC loss report and UO
follow AC loss will be
activated immediately.
Yes
: The ORBIT-14
is installed in
accordance with the
Czech telephony
requirements.
No
: No features are
changed.
Yes
: The ORBIT-14 is
installed in accordance
with UL requirements
for a Residential
Installation (UL 1641).
Operation of the unit’s
Digital Communicator
must be modified to
disable features which
are inappropriate for
UL listed installations.
This feature disables
the use of Upload/
Download and permits
a status display only
when remotely
accessed.
No
: No features are
disabled.
Comments on System Control 2 (Location 060: 2
nd
Digit)
Arm Pre-Warning
Alarm Restore
Yes
: When the system is Auto Armed, an
audible Exit Delay (warning) countdown will
commence 4 minutes prior to the automatic
arming. During this period, Exit Delay
beeps will be heard in the keypads.
No
: There is no Arm Pre-Warning for the
Auto Arming feature.
Yes
: The system will send an alarm restore after
the audible alarm “times out” (BTO=Bell Time
Out).
No
: The system will send an alarm restore when
the zone responsible for the alarm returns to its
non-violated (secured) state.