Functional description of PRxx1 series controllers Rev.H.doc
2016-10-28
37/43
[52] [FW] – Program the function for IO1 output line
See command [51]. Default value: <FW=07>.
[53] [FW] - Program the function for IO1 output line
See command [51]. Default value: <FW=00>.
[54] [FW] - Program the function for CLK output line
See command [51]. Default value: <FW=100>.
[55] [FW] - Program the function for DTA output line
See command [51]. Default value: <FW=100>.
Note: CLK and DTA lines are used for connection of PRT reader (Roger) or XM-2 module. If PRT
reader or XM-2 extension module is not connected to the controller then CLK and DAT lines can be
used as general purpose outputs. See also 2.2.3 RACS Clock and Data Interface.
[56] [FW] – Program the function for REL2 relay output line (only PR411DR controller)
See command [51]. Default value: <FW=07>.
[59] [FW] – Program the function for REL1 at XM-2 extension module (additional
output)
See command [51]. Default value: <FW=99>.
[60] [FW] - Program the function for REL2 at XM-2 extension module (additional
output)
See command [51]. Default value: <FW=07>.
[61][PP][QQ] - Specify RACS Clock&Data readers connected to the controller
[PP]=[00] – Terminal ID0 with RACS Clock&Data interface is disabled (see 2.2.3 RACS Clock and
Data Interface)
[PP]=[01] – Terminal ID0 with RACS Clock&Data interface is enabled (see 2.2.3 RACS Clock and
Data Interface)
[QQ]=[00] – Terminal with RACS Clock&Data interface is disabled (see 2.2.3 RACS Clock and Data
Interface)
[QQ]=[01] – Terminal with RACS Clock&Data interface is enabled (see 2.2.3 RACS Clock and Data
Interface)
[61] [RR][SS] – Specify Wiegand readers connected to the controller (only PR411DR)
[RR]=[xx] – Terminal ID0 with Wiegand interface (see Table 12)
[SS]=[xx] – Terminal ID1 with Wiegand interface (see Table 12)
Table 12. Types of Wiegand transmission modes
Code = [RR] and [SS]
Wiegand mode
[00]
Reader is disabled
[03]
Wiegand 26..66 bit, transmits PIN (HEX)
[24]
Wiegand 26..66 bit, transmits PIN (BIN)
[04]
Wiegand 26..66 bit, transmits card code
[05]
Wiegand 26..66 bit, transmits user ID (HEX)
[17]
Wiegand 26..66 bit, transmits user ID (BIN)
[15]
Wiegand 26..66 bit, transmits card code or PIN (HEX)
[16]
Wiegand 26..66 bit, transmits card code or PIN (BIN)