Functional description of PRxx1 series controllers Rev.H.doc
2016-10-28
32/43
III.
P
ROGRAMMING
Controllers of PRxx1 series can be programmed manually by means of keypad or remotely by
means of PC with PR Master software. More details on remote programming can be found in PR
Master manual. Manual programming can be executed by means of controller keypad (PR611 and
PR311SE) or by means of keypad on PRT reader connected to particular controller (the reader must
be equipped with keypad and configured to RACS Clock&Data interface, ID0 Terminal – see 2.2.3
RACS Clock and Data Interface). Manual programming consists in specifying User Commands (see
3.2 User Commands) and entering Installer Programming Mode (see 3.3 Installer Programming
Mode). User Functions enable management of cards and/or PINs and they can be used to control
some of the controller functions (e.g. Identification Mode, Door Mode). Installer Programming Mode
can be used for configuration of the controller, specifying functions for input and output lines as
well as other options.
If the access system is managed and programmed from PC it is critical not to use any other of
programming method otherwise system behavior can be corrupted because the computer database
will be de-synchronized from the settings entered manually.
Note: Installer Programming and User Commands can be entered by means of keypads of both the
controller (Terminal ID1) and external reader (Terminal ID0) connected to that controller.
3.1 Memory Reset
– Setting MASTER identifier and ID
address of the controller
Memory Reset results in clearing of all settings in the controller, restoring defaults and enables
setting of new MASTER card and/or PIN as well as new ID address of controller. After Memory
Reset, the controller automatically enters normal working mode and Armed Mode (LED STATUS
is red).
Note: If MASTER identifier (card and/or PIN) is not set then it is not possible to enter Installer
Programming Mode.
Simplified Memory Reset procedure
The procedure allows for specifying MASTER identifier (card) without setting controller ID address.
Remove CLK and DTA wires from terminals
Connect CLK wire with DTA wire
Restart the controller (switch power supply off/on or short RST contacts for a while) – all LED
indicators become active
Disconnect CLK and DTA wires— the LEDs shall be off, and then LED OPEN (green) shall
pulsate
While the LED OPEN is pulsing, read any card at the controller — this will be a new MASTER
card
The controller restarts automatically and switches to normal mode with address ID=00
Memory Reset procedure is finished and further adjustments (including ID address) can be
conducted in Installer Programming Mode (see 3.3 Installer Programming Mode) or by means of
User Commands (see 3.2 User Commands)
Simplified Memory Reset procedure for the controller without keypad (PR621 or
PR411DR)
The procedure results in clearing the controller settings, programming new MASTER card and
setting new ID address for the controller.
Remove CLK and IN3 wires from terminals
Connect CLK wire with IN3 wire