[01#] (SK) <MASTER> (SK) <INSTALLER> - Entry to Installer Programming Mode
Applied abbreviations and symbols are explained in 3.2 User Commands. Upon entering Installer
Programming Mode, LED SYSTEM (orange) and LED STATUS (red) are switched on. When
any key is pressed then both LEDs pulsate until command is property entered or any programming
error occurs. In case of error, the controller remains in Installer Programming Mode and long
acoustic signal is generated and both mentioned LEDs cease to pulsate. If command is entered
correctly then the controller generates OK signal (three short acoustic signals), both mentioned
LEDs cease to pulsate and the controller remains in Installer Programming Mode. Upon exiting the
Installer Programming Mode, the controllers returns to previous Armed or Disarmed Mode (see 2.6
Armed and Disarmed Modes). The controller exits Installer Programming Mode automatically after 4
minutes if no key is pressed or instantly if following command is entered:
[00#] - Exit from Installer Programming Mode
Installer Programming Mode is exited instantly
[40][MN] - Program the controller address (ID address)
Instead of [MN] enter required digits corresponding to the controller ID address (in range of 00-
99). Default value: <ID=00> or other value entered during Memory Reset (see 3.1 Memory Reset –
Setting MASTER identifier and ID address of the controller).
[41][P][FW] - Program the function for IN1 input line
[P] parameter specifies type of the input line i.e.: [P]=0 for NO (normally opened) or [P]=1 for NC
(normally closed). [FW] parameter specifies function of the input line (see 2.8 Inputs). Default
values: <FW=01>, [P] = 1.
[42][P][FW] - Program the function for IN2 input line
See command [41]. Default values: <FW=02>, [P] = 0.
[43][P][FW] - Program the function for IN3 input line
See command [41]. Default values: <FW=04>, [P] = 0.
[44][P][FW] - Program the function for IN4 input line (only PR411DR controller)
See command [41]. Default values: <FW=00>, [P] = 0.
[45][P][FW] - Program the function for IN5 input line (only PR411DR controller)
See command [41]. Default values: <FW=00>, [P] = 0.
[46][P][FW] - Program the function for IN6 input line (only PR411DR controller)
See command [41]. Default values: <FW=00>, [P] = 0.
[47][P][FW] - Program the function for IN7 input line (only PR411DR controller)
See command [41]. Default values: <FW=00>, [P] = 0.
[48][P][FW] - Program the function for IN8 input line (only PR411DR controller)
See command [41]. Default values: <FW=00>, [P] = 0.
[49][P][FW] - Program the function for IN1 input line at XM-2 extension module
(additional input)
See command [41]. Default values: <FW=00>, [P] = 0.
[50][P][FW] - Program the function for IN2 input line at XM-2 extension module
(additional input)
See command [41]. Default values: <FW=00>, [P] = 0.
[51] [FW] – Program the function for REL1 relay output line
[FW] parameter specifies function of the output line (see 2.9 Outputs). Default value: <FW=99>.