Functional description of PRxx1 series controllers Rev.H.doc
2016-10-28
29/43
[80]
Card or PIN mode
The output line is active when Card or PIN Identification
Mode at the controller is active (see 2.4 Identification
[81]
Card only mode
The output line is active when Card Only PIN Identification
Mode at the controller is active (see 2.4 Identification
[82]
PIN only mode
The output line is active when PIN Only Identification Mode
at the controller is active (see 2.4 Identification Modes).
[83]
Card and PIN mode
The output line is active when Card and PIN Identification
Mode at the controller is active (see 2.4 Identification
[97]
Entry door lock
The output is triggered for the time specified by means of
Door Unlock Time parameter if access is granted from ID0
Terminal. The output is intended for two way passages
where distinguishing of passage direction is required (e.g.
rotary gate) (see 2.7.2 Door Lock Control)
[98]
Exit door lock
The output is triggered for the time specified by means of
Door Unlock Time parameter if access is granted from ID1
Terminal. The output is intended for two way passages
where distinguishing of passage direction is required (e.g.
rotary gate), (see 2.7.2 Door Lock Control)
[99]
Door lock
The output is triggered for the time specified by means of
Door Unlock Time parameter regardless of Terminal at which
the access is granted. This is the standard output used for
door unlocking in most applications, (see 2.7.2 Door Lock
Control)
2.10 Function Keys
Function Keys are available at some PRT readers (Roger) and at PR311SE controller. User can
operate four Function Keys (if they are available at the keypads of Terminals ID0 and ID1), or two
Function Keys (if they are available at the keypad of Terminal ID0 or ID1). In RACS4 system it does
not matter if the Function Key is located at Terminal ID1 or ID0, as they can be programmed
individually in the same way by means of functions specified in Table 11.
Table 11: Function keys
Code
Name
Function
[00]
No function
No function is assigned to that key
[01]
Door bell
The key activates door bell.
[02]
Release door
The key releases door lock and door is opened as in case of
standard access granting
[04]
Key pressed (event
only)
Each use of key is only registered in event log. No other
action assigned to that function
[09]
Intruder alarm
The key activates
INTRUDER
flag (see 2.7.9 System Flags)
[60]
APB Register Reset
The key resets APB Register (see 2.7.15 Anti-passback Zones
[61]
Armed/Disarmed
The key switches the controller between Armed and
Disarmed Modes. The mode shall not be switched