Parameter Descriptions
2-163
7000-TD002A-EN-P – September 2007
Standard XIO Configurable Output 8 [StndXIO Config8]
Linear Number:
464
Default Value:
In Trq Limit
Access Level:
Advanced
Read/Write:
Read/Write
This parameter allows the user to select/configure output 8 on the Standard XIO board from a list of 28
available options. A 1 represents that the condition in the drive is true. The list is as follows:
Internal
Value
Enum Text
Description
0
Unassigned
The output is unassigned.
1
Reverse
Drive is running in Reverse direction.
2
Drv Stopping
Drive is Stopping
3
Auto Restart
Drive is in Auto Restart mode.
4
Drv Overload
Drive is running in an overload condition
5
Mtr Overload
Motor is running in an overload condition
6
Thermal Alrm
Drive has issued an alarm pertaining to its thermal performance
e.g. Loss of converter air flow in air cooled drives or loss of coolant
level in liquid cool drives.
7
Line Loss
Loss of line input voltage
8
CtrlPwr Loss
Loss of 120V AC Control Power
9
Test Mode
Drive is in Test Mode
10
At Speed
Drive is at commanded Speed
11
Sync Xfer
Synchronous transfer is enabled
12
On Bypass
Drive is running on Bypass
13
In Trq Limit
Drive is in Torque Limit
14
Drive Accel
Drive is accelerating
15
Drive Decel
Drive is decelerating
16
Jog
Drive is in Jog Mode
17
Remote
Drive is in Remote Mode
18
IsoFan1Ctctr
Turn Cooling Fan 1 in the Isolation Transformer cabinet
19
IsoFan2Ctctr
Turn Cooling Fan 2 in the Isolation Transformer cabinet
20
Field Enable
Field Current regulator is enabled (Synchronous motor only)
21
Field Start
Start command to the field regulator (Synchronous motor only)
22
Spd Cmd Loss
Speed Command Loss
23
Custom 1
Custom 1 Output
24
Custom 2
Custom 2 Output
25
Custom 3
Custom 3 Output
26
Custom 4
Custom 4 Output
27
Custom 5
Custom 5 Output
Contact Factory for availability.
Logix XIO Register A [Logix Register A]
Linear Number:
714
Default Value:
0
Minimum Value:
0
Maximum Value: 65535
Access Level:
Service
Read/Write:
Read/Write
This parameter is reserved for future-use only, and represents a register within the drive that will have the
ability to be written to remotely. There is no code in the firmware utilizing this register.
Содержание PowerFlex 7000
Страница 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Страница 2: ......
Страница 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Страница 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Страница 244: ......
Страница 282: ...2 238 Alphabetical Index 7000 TD002A EN P September 2007 This page is intentionally left blank ...
Страница 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Страница 349: ......