Parameter Descriptions
2-107
7000-TD002A-EN-P – September 2007
Adapter Loss Warning [DPI Loss Warning]
Linear Number:
148
Access Level:
Service
Read/Write:
Read
Only
This parameter specifies the DPI adapter loss warning. DPI is a polled communication network and if
that link is lost, the associated warning will occur. A ‘1’ represents an active warning.
Bit
Enum Text
Description
0
Adapter1Loss
Adapter 1 Loss Warning
1
Adapter2Loss
Adapter 2 Loss Warning
2
Adapter3Loss
Adapter 3 Loss Warning
3
Adapter4Loss
Adapter 4 Loss Warning
4
Adapter5Loss
Adapter 5 Loss Warning
5
Adapter6Loss
Adapter 6 Loss Warning
6
Spd Cmd Loss
Speed Command Loss Warning
7 Unused
8 Unused
9 Unused
10 Unused
11 Unused
12 Unused
13 Unused
14 Unused
15 Unused
XIO Adapter Loss [XIO Adaptr Loss]
Linear Number:
596
Access Level:
Service
Read/Write:
Read
Only
This parameter specifies the XIO adapter loss. There are 6 possible XIO slots, from Slot 1 to Slot 6. ‘1’
means the adapter is lost, ‘0’ means the adapter is still active if installed in the drive.
Bit
Enum Text
Description
0
XIO Card #1
Loss of XIO Board connected to Slot #1
1
XIO Card #2
Loss of XIO Board connected to Slot #2
2
XIO Card #3
Loss of XIO Board connected to Slot #3
3
XIO Card #4
Loss of XIO Board connected to Slot #4
4
XIO Card #5
Loss of XIO Board connected to Slot #5
5
XIO Card #6
Loss of XIO Board connected to Slot #6
6 Unused
7 Unused
Содержание PowerFlex 7000
Страница 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Страница 2: ......
Страница 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Страница 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Страница 244: ......
Страница 282: ...2 238 Alphabetical Index 7000 TD002A EN P September 2007 This page is intentionally left blank ...
Страница 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Страница 349: ......