Parameter Descriptions
2-41
7000-TD002A-EN-P – September 2007
Hardware Options 2 [HardwareOptions2]
Linear Number:
274
Default Value:
0000000000000000
Access Level:
Service
Read/Write:
Read/Write
This parameter allows the user to select additional hardware options. The options available are:
Bit
Enum Text
Description
0
Intgrl IsoTx
Integral Isolation Transformer installed in the drive
1 Unused
2 Unused
3 Unused
4 Unused
5 Unused
6 Unused
7 Unused
8 Unused
9 Unused
10 Unused
11 Unused
12 Unused
13 Unused
14 Unused
15 Unused
Number of Power Supplies [Number PwrSup]
Linear Number:
575
Default Value:
1
Minimum Value:
1
Maximum Value: 4
Access Level:
Service
Read/Write:
Read/Write when Stopped
This parameter specifies the total number of AC/DC power supplies installed in the drive. This number
includes the redundant power supply (if installed). In a multi power supply system there can only be one
redundant power supply.
Motor Ratings Parameters
Rated Motor Current [Rated Motor Amps]
Linear Number:
23
Default Value:
159 A
Minimum Value:
10 A
Maximum Value: 1500 A
Access Level:
Basic
Read/Write:
Read/Write when Stopped
This parameter specifies the rated full load current of the motor. This parameter is internally scaled and
used as the base value in all the drive per-unit calculations.
Содержание PowerFlex 7000
Страница 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Страница 2: ......
Страница 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Страница 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Страница 244: ......
Страница 282: ...2 238 Alphabetical Index 7000 TD002A EN P September 2007 This page is intentionally left blank ...
Страница 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Страница 349: ......