2-142 Parameter
Descriptions
7000-TD002A-EN-P – September 2007
Analog Inputs Parameters
Analog Input Configuration [Anlg Inp Config]
Linear Number:
652
Default Value:
0000000000000001
Access Level:
Service
Read/Write:
Read/Write when Stopped
This parameter configures the hardware circuitry used on the ACB for sensing the three analog inputs.
The inputs can be configured to either accept 0-10V (Voltage) input or 4-20mA (Current) input. The
default value configures Analog Input 1 as a 4-20mA input.
Bit
Enum Text
Description
0
An1 0=V 1=mA
Analog Input 1 enter – 0 for Voltage; 1 for Current
1
An2 0=V 1=mA
Analog Input 2 enter – 0 for Voltage; 1 for Current
2
An3 0=V 1=mA
Analog Input 3 enter – 0 for Voltage; 1 for Current
3 Unused
4 Unused
5 Unused
6 Unused
7 Unused
8 Unused
9 Unused
10 Unused
11 Unused
12 Unused
13 Unused
14 Unused
15 Unused
Speed Pot Minimum Voltage [Speed Pot Vmin]
Linear Number:
630
Default Value:
0.00 V
Minimum Value:
-10.00 V
Maximum Value: 10.00 V
Access Level:
Service
Read/Write:
Read/Write when Stopped
This parameter specifies the minimum output voltage from the speed potentiometer and is used for
calibrating the speed command.
Содержание PowerFlex 7000
Страница 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Страница 2: ......
Страница 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Страница 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Страница 244: ......
Страница 282: ...2 238 Alphabetical Index 7000 TD002A EN P September 2007 This page is intentionally left blank ...
Страница 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Страница 349: ......