2-84 Parameter
Descriptions
7000-TD002A-EN-P – September 2007
External Fault 7 Class [ExtFault7 Class]
Linear Number:
206
Default Value:
Class2 Fault
Access Level:
Basic
Read/Write:
Read/Write
This parameter specifies the class of the external fault 7. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable
This disables the fault input.
Class1 Fault
The drive will shut down immediately
Class2 Fault
The drive will perform a controlled shut down
Warning
The drive will not shut down but a warning will be displayed
External Fault 8 Class [ExtFault8 Class]
Linear Number:
207
Default Value:
Class2 Fault
Access Level:
Basic
Read/Write:
Read/Write
This parameter specifies the class of the external fault 8. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable
This disables the fault input.
Class1 Fault
The drive will shut down immediately
Class2 Fault
The drive will perform a controlled shut down
Warning
The drive will not shut down but a warning will be displayed
External Fault 9 Class [ExtFault9 Class]
Linear Number:
410
Default Value:
Class2 Fault
Access Level:
Basic
Read/Write:
Read/Write
This parameter specifies the class of the external fault 9. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable
This disables the fault input.
Class1 Fault
The drive will shut down immediately
Class2 Fault
The drive will perform a controlled shut down
Warning
The drive will not shut down but a warning will be displayed
External Fault 10 Class [ExtFault10 Class]
Linear Number:
411
Default Value:
Class2 Fault
Access Level:
Basic
Read/Write:
Read/Write
This parameter specifies the class of the external fault 10. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable
This disables the fault input.
Class1 Fault
The drive will shut down immediately
Class2 Fault
The drive will perform a controlled shut down
Warning
The drive will not shut down but a warning will be displayed
Содержание PowerFlex 7000
Страница 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Страница 2: ......
Страница 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Страница 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Страница 244: ......
Страница 282: ...2 238 Alphabetical Index 7000 TD002A EN P September 2007 This page is intentionally left blank ...
Страница 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Страница 349: ......