Parameter Descriptions
2-65
7000-TD002A-EN-P – September 2007
Ramp Speed 2 [Ramp Speed 2]
Linear Number:
74
Default Value:
12.0 Hz
Minimum Value:
5.0 Hz
Maximum Value: 100.0 Hz
Access Level:
Advanced
Read/Write:
Read/Write
This parameter specifies the second break point in the speed ramp. It must be greater than Ramp Speed 1.
Ramp Speed 3 [Ramp Speed 3]
Linear Number:
75
Default Value:
54.0 Hz
Minimum Value:
5.0 Hz
Maximum Value: 100.0 Hz
Access Level:
Advanced
Read/Write:
Read/Write
This parameter specifies the third break point in the speed ramp. It must be greater than Ramp Speed 2.
Ramp Speed 4 [Ramp Speed 4]
Linear Number:
76
Default Value:
60.0 Hz
Minimum Value:
5.0 Hz
Maximum Value: 100.0 Hz
Access Level:
Advanced
Read/Write:
Read/Write
This parameter specifies the fourth break point in the speed ramp. It must be greater than Ramp Speed 3.
S Curve Percent [S Curve Percent]
Linear Number:
475
Default Value:
0 %
Minimum Value:
0 %
Maximum Value: 100 %
Access Level:
Advanced
Read/Write:
Read/Write
This parameter specifies the non-linear part of the S-curve acceleration profile expressed as percentage
of the total S-curve profile. Set this parameter to 0% to disable S-curve Profile and allow Ramp Profile to
be the active profile.
S Curve Acceleration Time 1 [S Curve Accel 1]
Linear Number:
481
Default Value:
20.0 sec
Minimum Value:
0.0 sec
Maximum Value: 1200.0 sec
Access Level:
Advanced
Read/Write:
Read/Write
This parameter specifies the total acceleration time when the S-Curve starting profile is selected, and the
acceleration 1 time is chosen through DPI logic command. This is the default time when S-Curve is
enabled.
Содержание PowerFlex 7000
Страница 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Страница 2: ......
Страница 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Страница 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Страница 244: ......
Страница 282: ...2 238 Alphabetical Index 7000 TD002A EN P September 2007 This page is intentionally left blank ...
Страница 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Страница 349: ......