2-24 Parameter
Descriptions
7000-TD002A-EN-P – September 2007
Parameter Error [Parameter Error]
Linear Number:
597
Minimum Value:
0
Maximum Value: 65535
Access Level:
Basic
Read/Write:
Read
Only
This parameter specifies the linear number of the parameter in the database having a value that’s out of
range. Only one parameter linear number can be specified at a time in the parameter error. This means
that more than one parameter can have an error but only one of them is specified.
Feature Select Parameters
Operating Mode [Operating Mode]
Linear Number:
4
Default Value:
Normal
Access Level:
Monitor
Read/Write:
Read/Write when Stopped
This parameter specifies the operating modes of the drive. It is not saved and is set to Normal at power
up. This parameter cannot be changed when the drive is running. Refer to the Chapter 1 – Functional
Description in the PowerFlex 7000 User Manual for detailed description of the test modes.
The possible operating modes are:
Normal
Normal operating mode
Gate Test
Gate Test mode (medium voltage off)
DC Current
DC Current test mode
System Test
System Test mode (medium voltage off)
Open Circuit
Open Circuit test mode (needs output contactor or disconnected motor)
Open Loop
Open Loop test mode (for induction motors only)
Содержание PowerFlex 7000
Страница 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Страница 2: ......
Страница 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Страница 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Страница 244: ......
Страница 282: ...2 238 Alphabetical Index 7000 TD002A EN P September 2007 This page is intentionally left blank ...
Страница 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Страница 349: ......