2-128 Parameter
Descriptions
7000-TD002A-EN-P – September 2007
Tachometer Type [Tach Type]
Linear Number:
233
Default Value:
None
Access Level:
Basic
Read/Write:
Read/Write when Stopped
This parameter specifies the type of tachometer or encoder installed. Warning: If tachometer type is set
to Single, the drive cannot determine the direction of rotation when the motor is coasting. If the direction
of rotation is not the same as the commanded direction, a flying start will not be successful.
The following types are available:
None
No tach installed
Single
Single output (non-directional)
Quadrature
Quadrature outputs (directional)
Absolute Enc
Absolute encoder
Sine-Cos Inc
Not active
Sine-Cos Z
Not active
Sine-Cos SSI
Not active
Contact factory for availability.
Tachometer Pulses per Revolution [Tach PPR]
Linear Number:
234
Default Value:
1024 PPR
Minimum Value:
120 PPR
Maximum Value: 4096 PPR
Access Level:
Basic
Read/Write:
Read/Write when Stopped
This parameter specifies the number of pulses produced by the tachometer in one revolution. This
parameter is not used for absolute encoders.
Encoder Offset
[Encoder Offset]
Linear Number:
644
Default Value:
0 deg
Minimum Value:
0 deg
Maximum Value: 360 deg
Access Level:
Advanced
Read/Write:
Read/Write
This parameter specifies the offset of the encoder. This parameter is required because an encoder is
used for both speed and position.
Contact Factory for availability.
Содержание PowerFlex 7000
Страница 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Страница 2: ......
Страница 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Страница 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Страница 244: ......
Страница 282: ...2 238 Alphabetical Index 7000 TD002A EN P September 2007 This page is intentionally left blank ...
Страница 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Страница 349: ......