Functional Description 1-35
7000-TD002A-EN-P – September 2007
PID Process Control
The PID process control feature is now integrated into the PowerFlex
7000 drive. The PID controller provides a single closed loop process
control with proportional, integral and derivative control action. This
feature is designed to eliminate the need for external control devices
in applications that require control of a process.
The drive reads the
Process Variable
(357) from the analog input
that is fed by the customer process sensor and compares it to the
desired
Process Setpoint
(360). The analog I/O is either in the
voltage range of 0 -10V or in the current range of 4 – 20 mA. The
algorithm will then adjust the
PID Output
(356), changing the drive’s
speed command frequency to make the
Process Variable
equal to the
Process Setpoint
. The internal PID process controller uses the
velocity form algorithm of the PID equation. This signifies that the
loop works on the change in error to adjust the output whereas a
traditional positional form algorithm works on the error directly.
The firmware provides several options as to the way the algorithm
works. Independent or dependent gain form can be chosen by the
Indpndt Gain
bit in the
PID Output
(356). The difference should be
taken into consideration when tuning the PID parameters;
PID Gain
(353),
PID Integral Time
(354) and
PID Derivative Time
(355). The
equations for the algorithms in dependent and independent gain form
are shown below:
Dependent Gain Form:
In this form of algorithm, the
PID gain
is working as a controller
gain. The change in the
PID Gain
will affect all three terms;
proportional, integral, and derivative.
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
Δ
+
−
+
Δ
+
Δ
+
=
−
−
−
t
E
E
E
T
t
E
T
E
K
PO
PO
n
n
n
d
l
P
n
n
2
1
1
2
1
Independent Gain Form
In this form of algorithm, the
PID gain
is working as a proportional
gain. The change in the
PID Gain
will affect only the proportional
term.
t
E
E
E
T
t
E
T
E
K
PO
PO
n
n
n
d
l
P
n
n
Δ
+
−
+
Δ
+
Δ
+
=
−
−
−
2
1
1
2
1
where: PO:
PID Output
E: Error (
Process Setpoint
-
Process Variable
)
t
Δ
: Sampling Period used by the loop
K
p
:
PID Gain
T
l
:
PID Integral Time
in seconds
T
d
:
PID Derivative Time
in seconds
Contact factory for the availability of this feature.
Содержание PowerFlex 7000
Страница 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Страница 2: ......
Страница 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Страница 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Страница 244: ......
Страница 282: ...2 238 Alphabetical Index 7000 TD002A EN P September 2007 This page is intentionally left blank ...
Страница 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Страница 349: ......