3-42
DBT Reach Drive User Manual
Sets the responsiveness of the bus regulator.
Sets the method and sequence of the DC bus regulator voltage. Choices are dynamic
brake, frequency adjust, or both.
Sequence is determined by programming or digital input to the terminal block.
If a dynamic brake resistor is connected to the drive, Bus Reg Mode A and Bus Reg
Mode B must be set to option 2, 3, or 4.
160
Bus Reg Ki
Range:
0 to 5000 [1]
Default:
450
Access:
2
Path:
Dynamic Control>Stop/Brake Modes
See also:
161, 162
161
162
Bus Reg Mode A
Bus Reg Mode B
Range:
0 = Disabled
1 = Adjust Freq
2 = Dynamic Brak
3 = Both - DB 1st
4 = Both - Frq 1st
Default:
Mode A: 0 = Disabled
Mode B: 0 = Disabled
Access:
2
Path:
Dynamic Control>Stop/Brake Modes
See also:
160, 163