3-14
DBT Reach Drive User Manual
Value of volts dropped across the resistance of the motor stator. Used only when
Motor Cntl Sel (53) is set to Sensrls Vect, SV Economize or FVC Vector.
Value of amps for full motor flux. Used only when Motor Cntl Sel (53) is set to Sensrls
Vect, SV Economize or FVC Vector.
Sets the value of the voltage drop across the leakage inductance of the motor at rated
motor current. Used only when Motor Cntl Sel (53) is set to Sensrls Vect, SV
Economize or FVC Vector.
Specifies motor torque applied to the motor during the flux current and inertia tests
performed during an autotune.
62
IR Voltage Drop
Range:
0.0 to Motor NP Volts x 0.25 [0.1 VAC]
Default:
Based on Drive Rating
Access:
1
Path:
Motor Control>Torq Attributes
See also:
53, 61
63
Flux Current Ref
Range:
0.00 to Motor NP FLA [0.01 Amps]
Default:
Based on Drive Rating
Access:
1
Path:
Motor Control>Torq Attributes
See also:
53, 61
64
Ixo Voltage Drop
Range:
0.00 to 230.0, 460.0 or 575.0 VAC [0.1 VAC]
Default:
Based on Drive Rating
Access:
1
Path:
Motor Control>Torq Attributes
See also:
66
Autotune Torque
Range:
0.0 to 150% [0.1%]
Default:
50%
Access:
1
Path:
Motor Control>Torq Attributes
See also:
53
FV