3-8
DBT Reach Drive User Manual
Set to the motor nameplate rated frequency. The motor nameplate base frequency
defines the output frequency when operating at rated voltage, rated current, rated
speed, and rated temperature.
Set to the motor nameplate rated RPM. The motor nameplate RPM defines the rated
speed when operating at motor nameplate base frequency, rated current, base
voltage, and rated temperature. This is used to calculate slip.
Set to the motor nameplate rated power. The motor nameplate power is used with the
other nameplate values to calculate default values for motor parameters to assist the
commissioning process. This may be entered in horsepower or in kilowatts as
selected in Mtr NP Pwr Units (46).
Selects the motor power units to be used. This parameter determines the units for
Motor NP Power (45).
Convert HP = Converts all power units to Horsepower.
Convert kW = Converts all power units to kilowatts.
43
Motor NP Hertz
Range:
5.0 to 400.0 Hz [0.1 Hz]
Default:
Based on Drive Type
Access:
1
Path:
Motor Control>Motor Data
See also:
44
Motor NP RPM
Range:
60.0 to 25200.0 RPM [0.1 RPM]
Default:
1780 RPM
Access:
1
Path:
Motor Control>Motor Data
See also:
45
Motor NP Power
Range:
0.00 to 1000.00 [0.01 kW or 0.01 HP]
Default:
Based on Drive Type
Access:
1
Path:
Motor Control>Motor Data
See also:
46
46
Mtr NP Pwr Units
Range:
0 = Horsepower (changes power units to HP without rescaling values)
1 = kilowatts (changes power units to kW without rescaling values)
2 = Convert HP (Converts all power units to HP and rescales values)
3 = Convert kW (changes power units to kW and rescales values)
Default:
Based on Drive Rating
Access:
2
Path:
Motor Control>Motor Data
See also:
Содержание CNMD180W0ENNNC1
Страница 1: ...Instruction Manual Reach Drive User Manual Manufactured for DBT D2 3561 ...
Страница 206: ...B 4 DBT Reach Drive Manual ...
Страница 238: ...Appendix D 24 DBT Reach Drive User Manual ...
Страница 247: ......