Parameter Descriptions
3-7
The drive rated output current.
The Main Control board software version.
Set to match the type of motor connected: Induction, Synchronous Reluctance, or
Synchronous Permanent Magnet.
Important:
Selecting option 1 or 2 also requires selection of “Custom V/Hz,” option 2
in Motor Cntl Sel (53).
Set to the motor nameplate rated volts. The motor nameplate base voltage defines the
output voltage when operating at rated current, rated speed, and rated temperature.
Set to the motor nameplate rated full load amps. The motor nameplate FLA defines
the output amps when operating at rated voltage, rated speed, and rated temperature.
It is used in the motor thermal overload and in the calculation of slip.
29
Control SW Ver
Range:
0.000 to 65535.000 [0.001]
Default:
Read Only
Access:
0
Path:
Monitor>Drive Data
See also:
196
40
Motor Type
Range:
0 = Induction
1 = Synchr Reluc
2 = Synchr PM
Default:
0 = Induction
Access:
2
Path:
Motor Control>Motor Data
See also:
53, 157, 158, 159
41
Motor NP Volts
Range:
0.0 to Drive Rated Volts [0.1 VAC]
Default:
Based on Drive Rating
Access:
1
Path:
Motor Control>Motor Data
See also:
42
Motor NP FLA
Range:
0.0 to Rated Amps x 2 [0.1 Amps]
Default:
Based on Drive Rating
Access:
1
Path:
Motor Control>Motor Data
See also:
47, 48