Speed Reg (1) =
Drive operates as a speed regulator.
Torque Reg (2) =
An external torque reference is used for the torque command.
Min Torq/Spd (3) =
Selects the smallest algebraic value to regulate to when the
torque reference and torque generated from the speed regulator are compared.
Max Torq/Spd (4) =
Selects the largest algebraic value to regulate to when the torque
reference and torque generated from the speed regulator are compared.
Sum Torq /Spd (5) =
Selects the sum of the torque reference and the torque
generated from the speed regulator.
Absolute Min (6) =
Selects the smallest absolute algebraic value to regulate to when
the torque reference and torque generated from the speed regulator are compared.
Pos/Spd Prof (7) =
Drive operates as a speed or position regulator as determined by
the steps configured by the Profile Step parameters (720-877) and Setup parameters
(705-719).
Selects the only control source for these logic commands:
•
Start (Run)
•
Jog
•
Direction
•
Clear Faults
•
Stop (Any attached HIM Stop Key is always functional. A Network stop command is
effective only for Network or All Ports. A Terminal Block Stop command is effective
only for Terminal Blk or All Ports.
Selecting All Ports (7) enables control from any control source (or port).
89
Logic Source Sel
Range:
0 = Terminal Blk
1 = Local HIM
2 = DPI Port 2
3 = DPI Port 3
4 = Reserved
5 = Network
6 = Reserved
7 = All Ports
Default:
1 = Local HIM
Access:
0
Path:
Speed Command>Control Src Sel
See also: