3-84
DBT Reach Drive User Manual
Analog In 1 Hi sets the highest input value to the analog input 1 scaling block.
Anlg ln Config (320) defines if the input value will be -/+10V or 0-20 mA.
Sets the lowest input value to the analog input 1 scaling block.
Anlg ln Config (320) defines if the input value will be -/+10V or 0-20 mA.
If set below 4 mA, Analog ln x Loss (324) should be “Disabled.”
322
Analog In 1 Hi
Range:
0.000 to 20.000 mA [0.001 mA]
-/+10.000 V [0.001 V]
0.0 to 10.000 V [0.001 V]
Default:
20.000 mA
Access:
0
Path:
Inputs & Outputs>Analog Inputs
See also:
91, 92
Analog Input Scaling Example
Assume:
Speed Ref A Sel = Analog In 1
Minimum Freq = 0 Hz
Maximum Freq = 60 Hz
Analog In 1 Lo = 0.0 V
Analog In 1 Hi = 10.0 V
This is the default setting, where minimum input (0 V) represents Minimum Speed
and maximum input (10 V) represents Maximum Speed.
323
Analog In 1 Lo
Range:
0.000 to 20.000 mA [0.001 mA]
-/+10.000 V [0.001 V]
0.0 to 10.000 V [0.001 V]
Default:
4.000 mA
Access:
0
Path:
Inputs & Outputs>Analog Inputs
See also:
91, 92