DBT Reach Drive User Manual
Selects drive response when an analog signal loss is detected. Signal loss is defined
as an analog signal less than 1 V or 2 mA. The signal loss event ends and normal
operation resumes when the input signal level meets or exceeds 1.5 V or 3 mA.
One of the selections (1=Fault) stops the drive on signal loss. All other choices make it
possible for the input signal to return to a usable level while the drive is still running.
Selects the mode for analog outputs.
327 Analog In 2 Loss
Range:
0 = Disabled
1 = Fault
2 = Hold Input (use last frequency command)
3 = Set Input Lo (use Minimum Speed as frequency command)
4 = Set Input Hi (use Maximum Speed as frequency command)
5 = Go to Preset1 (use Preset1 as frequency command)
6 = Hold OutFreq (maintain last output frequency)
Default:
0 = Disabled
Access:
2
Path:
Inputs & Outputs>Analog Inputs
See also:
91, 92
!
ATTENTION:
Setting parameter 327 to a value greater than 1 allows the
input signal to return to a usable level while the drive is running. If a lost
analog signal is restored while the drive is running, the drive will ramp to
the restored reference level at the rate specified in Accel Time 1 (140),
Accel Time 2 (141), Decel Time 1 (142), and Decel Time 2 (143). Be
aware that an abrupt speed change may occur depending upon the new
reference level and the rate specified in these parameters. Failure to
observe this precaution could result in bodily injury.
340
Analog Out Config
Range:
See figure 3.33
Default:
See figure 3.33
Access:
0
Path:
Inputs & Outputs>Analog Outputs
See also:
Figure 3.33 – Analog Out Config
1
x
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=Current
0
=Voltage
x =Reserved
Bit #
Factory Default Bit Values
Analog Out1
Analog Out2
Содержание CNMD180W0ENNNC1
Страница 1: ...Instruction Manual Reach Drive User Manual Manufactured for DBT D2 3561 ...
Страница 206: ...B 4 DBT Reach Drive Manual ...
Страница 238: ...Appendix D 24 DBT Reach Drive User Manual ...
Страница 247: ......