3-38
DBT Reach Drive User Manual
Sets the percentage of acceleration or deceleration time that is applied to the ramp as
S Curve. Time is added; 1/2 at the beginning and 1/2 at the end of the ramp.
Selects the source for the adjustment of current limit (i.e., parameter, analog input,
etc.).
Defines the current limit value when Current Lmt Sel (147) = Cur Lim Val.
When in Adj Voltage mode, the output voltage will not be allowed the exceed this
value.
Sets the responsiveness of the current limit.
146
S Curve %
Range:
0 to 100% [0.1%]
Default:
0%
Access:
0
Path:
Dynamic Control>Ramp Rates
See also:
140 - 143
147
Current Lmt Sel
Range:
0 = Curr Lim Val
1 = Analog In 1
2 = Analog In 2
Default:
0 = Cur Lim Val
Access:
2
Path:
Dynamic Control>Load Limits
See also:
146, 149
148
Current Lmt Val
Range:
Based on Drive Type [0.1 Amps]
Default:
Rated Amps x 1.5 (Yields approximate default value)
Access:
0
Path:
Dynamic Control>Load Limits
See also:
147, 149
149
Current Lmt Gain
Range:
0 to 5000 [1]
Default:
250
Access:
2
Path:
Dynamic Control>Load Limits
See also:
147, 148