Fault
Possible cause
Remedy
No measurement signal
Connecting cable loose
Check the secondary terminals,
Damaged transformer
Check transformer and replace if
necessary
Faulty measurement signal
Incorrect frequency
Frequency according to
Ò
Rating
plate
Connections connected wrong
way round
Arrange connecting cables cor‐
rectly
Damaged transformer
Check transformer and replace if
necessary
Thermal stresses of the primary
screw fitting
Loose screw on the primary con‐
nection
Check the primary connection,
Thermal stresses of the primary
screw fitting
Insufficient cross-sections of the
busbars
Use bus bars with a larger cross-
section,
Thermal stresses of the secon‐
dary screw fitting
Loose screw on secondary clamp Check the secondary terminals,
Insufficient cross-sections of the
connecting cables
Use connecting cables with a
larger cross-section,
High voltage on the transformer
base
Incorrect assembly, the trans‐
former not earthed
Check the connections,
Check the earthing measures,
Limited device function through
overheating of the secondary
winding
Overload (the burden is higher
than the specified limit power)
Burden according to the informa‐
tion on the device's rating plate
Limited device function through
overheating of the primary
winding
Short circuit in the secondary
winding(s)
Contact the responsible sales
representative or the manufac‐
turer,
Limited device function through
overheating of the primary circuit
Current-carrying connections not
screwed correctly
Check the connections according
to
Damage to the high voltage insu‐
lation during operation
Leakage
Immediately interrupt the run‐
ning operation and contact the
responsible sales representative
or the manufacturer
Greatly increased partial dis‐
charges
ICO 72,5...245
USER MANUAL
When to interrupt the running operation
31/47