» Check the composite insulator for damage to and between the
insulator shields. If you notice any abnormalities, proceed as
described here:
Chapter 1.3.5 What should you do in the
» Clean the insulator if necessary. In this regard follow the
instructions as described under
3.
Check the oil level:
Check the transformer for oil leaks.
Check the oil level using the oil level indicator on the head of the
transformer (see Fig.). For further information please refer to
1
Fig. 6: Position of the oil level indicator on the ICO type current trans‐
former
1 Oil level indicator
è
The oil level indicator should be in the green area.
4.
Prepare the transformer for connection on the primary side:
Always ensure a conductive contact at the primary connection
plates. If available, completely remove the protective coating (wax
emulsion) from the contact surfaces.
ICO 72,5...245
USER MANUAL
How to use this device as intended
16/47