Type
ICO 72.5
ICO 123
ICO 145
ICO 170
ICO 245
Standard values
for insulation
Rated withstand AC
voltage (50 Hz/1 min.)
140 kV
230 kV
275 kV
325 kV
460 kV
Rated lightning impulse
withstand voltage
(1,2/50
m
s)
325 kV
550 kV
650 kV
750 kV
1050 kV
insulating class
E
Device-specific data
Deviating, customer-specific values are possible! For these speci‐
fications and other information required for operation of the trans‐
former (e. g. accuracy class, rated voltage, burden power, etc.)
please refer to the rating plate.
5.2 Environmental conditions
For deviating environmental conditions, see
Ò
Datasheet and
Ò
Rating
plate. Observe the following instructions:
» Never use the device in areas at risk of explosion.
» Never use the device near easily flammable materials.
Installation altitude
Up to 1000 m above sea level
1
1
This information refers to the standard version of the device. Modifica‐
tions for greater heights are possible. Please contact your sales partner
or get in touch with us directly
Chapter 7 Contact / customer service
Rated operating conditions
Temperature class
-25°C to +40 °C
ICO 72,5...245
USER MANUAL
Technical data