2.3 Installation
2.3.1 Installing the device
Before you start the installation, think about your safety!
DANGER
High voltage in conductive components
There is danger to life through electric shock! Observe the
5 safety rules of electrical engineering.
» Disconnect the source of high voltage.
» Safeguard against reconnection.
» Ensure no voltage is present.
» Earth.
» Block off adjacent live parts.
1.
Connect the transformer mechanically to the switchgear:
» Maintain the insulation distance between system components
and live surfaces!
» If present, remove the transport protection. Do not make any
structural changes to the transformer
» Ensure that the installation surface is even.
» Level out any unevenness between the transformer and the
installation surface.
» The position of the transformer during installation is upright.
» Secure the transformer to the foundation. For fixing dimen‐
sions please refer to the
Ò
Dimensional drawing. Depending
on the diameter of the drilled hole we recommend the fol‐
lowing bolt size:
Drilled hole
Æ
[
mm
]
Bolt size
18
M16
24
M20
» The required tightening torques are shown in the table, refer
to
2.
Ensure that the composite insulator is in perfect working order:
Fig. 5: Disconnect
mains!
ICO 72,5...245
USER MANUAL
How to use this device as intended
15/47