» An oil drain screw enables access to the oil chamber in the trans‐
former base. The oil level indicator on the head of the transformer
is optimised for the operator's viewing angle.
» Four transport eyes on the transformer base facilitate proper han‐
dling during installation.
For further information or details regarding the shield shape, flash‐
over distance and creepage path, please refer to the
Ò
Dimensional
drawing.
The device meets the relevant VDE-, IEC- and EN-standards. You will
find the electrical data on the
Ò
Rating plate.
The type designation and specification of the device can be found
on the
Ò
Datasheet and the device's
Ò
Rating plate. The rating
plate is usually located at the front of the secondary terminal box.
Upon request, the ICO type transformer will be factory designed to
meet all national and international standards including IEEE /
ANSI, CSA, IEC as well as all customer requirements.
1.1.2 What is the purpose of the device?
The task of the current transformer is to transfer currents proportion‐
ally and phase-true such that they are detectable for measuring equip‐
ment at low potential.
The current transformer translates high currents into lower, directly
measurable currents, which are adapted to the downstream secondary
technology. The electrical configurations are suitable for digital and
conventional measuring and protection devices.
-
Depending on the version,
-
the ICO type current transformer is suit‐
able for use at a maximum voltage for operating equipment (U
m
) of
72,5 kV, 123 kV, 145 kV, 170 kV or 245 kV.
The ICO type current transformers can be equipped with windings for
measuring and protection purposes. They are intended for use in
» switchgear, switching device combinations,
» power distribution systems in connection with secondary devices
(relays, meters, indication instruments).
ICO 72,5...245
USER MANUAL
Read first, then take action!
6/47