TECHNICAL ASSISTANCE SERVICE
54
Error
code via
QAA
Diagnostic
info
Description of error
Type of fault
System action
Procedure
140
521
Illegal LPB address
Illegal segment number
or LPB device number
Message
Contact Technical
Assistance Service
148
517
Interface/base unit LPB
incompatibility
LPB incompatibility
between interface unit
and base unit
Message
Contact Technical
Assistance Service
151
1
Internal control board
error
Software error or internal
error
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
151
…
Internal control board
error
Software error or internal
error
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
151
632
Internal control board
error
Software error or internal
error
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
152
6
Parameter setting error
Wrong setting
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
152
…
Parameter setting error
Wrong setting
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
152
610
Parameter setting error
Wrong setting
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
153
259
Lockout caused by unit Generic error or internal
error
Burner lockout
(permanent). Lockout
reset required
Undefined software error.
Reset the control card
154
400
Generic error
The boiler return
temperature is above the
safety threshold (boiler
tempe Sd_RL_
groesser_VL)
Safety shutdown
OEM parameter not
editable via QAA.
Generic error. Check
the system. Return
temperature too high
154
401
Generic error
The boiler return
temperature is above
or equal to the boiler
tempe Sd_RL_
groesser_VL - 2K)
Safety shutdown
OEM parameter not
editable via QAA.
Generic error. Check
the system. Return
temperature too high
154
402
Generic error
No further differentiation
Safety shutdown
Undefined software error
154
404
Generic error
Error 400 has occurred
more times than
permitted by the burner
parameter GrenzeRL_
groesserVL
Burner lockout
(permanent). Lockout
reset required
OEM parameter not
editable via QAA.
Generic error. Check
the system. Return
temperature too high
154
425
Generic error
Error 426 has occurred
more times than
permitted by the
burner parameter
GrenzeGradient
Burner lockout
(permanent). Lockout
reset required
OEM parameter not
editable via QAA.
Generic error. Check
the system. Boiler
temperature rises too
quickly
154
426
Generic error
Boiler temperature has
risen more quickly than
permitted by parameter
TempGradMax
Safety shutdown
OEM parameter not
editable via QAA.
Generic error. Check
the system. Boiler
temperature rises too
quickly
Содержание TAU 150 UNIT