TECHNICAL ASSISTANCE SERVICE
39
If a remote storage cylinder (accessory) is present,
connect the storage cylinder temperature sensor to the
control panel and set the manufacturer level parameter
“558b2”=0 (see the “Manufacturer level” section).
- Press the
R
key.
Press the
+
-
keys to adjust the setpoint.
Press any of the keys to exit
R
T
M
V
.
The new setting is stored in memory.
If the remote storage cylinder has its own thermostat,
leave the manufacturer level parameter “558b2” = 1 (see
the “Manufacturer level” section). .
- If an outdoor temperature sensor is installed, set instal-
ler parameter “532 Heating curve slope heating circuit
1” as instructed in the section “Setting functioning
parameters”.
If any boiler ignition or functioning errors are detected,
the display shows the type of error.
Errors can be of two types:
- PERMANENT errors are those that can only be cancel-
led by pressing the
S
key.
- TRANSIENT errors are those that are automatically
cancelled as soon as the cause is rectified (see “Error
codes” on page 51).