TECHNICAL ASSISTANCE SERVICE
49
Error
code via
QAA
Diagnostic
info
Description of error
Type of fault
System action
Procedure
0
0
No input code
No input code
-
-
0
473
No input code
No input code
Message
-
10
150
Outdoor temperature
sensor error
Short circuit in outdoor
temperature sensor
Message
Check/replace outdoor
temperature sensor
10
151
Outdoor temperature
sensor error
Outdoor temperature
sensor faulty
Message
Check/replace outdoor
temperature sensor
20
142
Boiler sensor 1 error
Short circuit in
temperature sensor B2
Safety shutdown
Check/replace
temperature sensor
20
143
Boiler sensor 1 error
Temperature sensor B2
faulty
Safety shutdown
Check/replace
temperature sensor
20
405
Boiler sensor 1 error
Boiler sensor 1 error
Safety shutdown
Check/replace
temperature sensor
20
406
Boiler sensor 1 error
Boiler sensor 1 error
Safety shutdown
Check/replace
temperature sensor
20
410
Boiler sensor 1 error
Short circuit in
temperature sensor B2
Burner lockout
(permanent). Lockout
reset required
Check/replace
temperature sensor
20
411
Boiler sensor 1 error
Temperature sensor B2
faulty
Burner lockout
(permanent). Lockout
reset required
Check/replace
temperature sensor
20
412
Boiler sensor 1 error
No further differentiation
Burner lockout
(permanent). Lockout
reset required
Check/replace
temperature sensor
20
413
Boiler sensor 1 error
No further differentiation
Burner lockout
(permanent). Lockout
reset required
Check/replace
temperature sensor
28
152
Flue gas sensor error
Short circuit in
temperature sensor
Message
Check/replace flue gas
temperature sensor
28
153
Flue gas sensor error
Temperature sensor
faulty
Message
Check/replace flue gas
temperature sensor
28
507
Flue gas sensor error
Temperature reading not
plausible
Safety shutdown
Check/replace flue gas
temperature sensor
32
524
CH flow sensor 2 error
Short circuit in CH 2
temperature sensor
Message
Check/replace
temperature sensor
32
525
CH flow sensor 2 error
CH 2 temperature sensor
faulty
Message
Check/replace
temperature sensor
32
546
CH flow sensor 2 error
Short circuit in additional
zone clip-in temperature
sensor (accessory)
Message
Check/replace
temperature sensor
32
547
CH flow sensor 2 error
Additional zone clip-in
temperature sensor
faulty (accessory)
Message
Check/replace
temperature sensor
40
144
CH return sensor 1 error
Short circuit in return
temperature sensor (B7)
Safety shutdown
Check/replace
temperature sensor
40
145
CH return sensor 1 error
Return temperature
sensor (B7) faulty
Safety shutdown
Check/replace
temperature sensor
40
407
CH return sensor 1 error No further differentiation
Safety shutdown
Check/replace
temperature sensor
40
408
CH return sensor 1 error No further differentiation
Safety shutdown
Check/replace
temperature sensor
40
414
CH return sensor 1 error
Short circuit in return
temperature sensor (B7)
Burner lockout
(permanent). Lockout
reset required
Check/replace
temperature sensor
40
415
CH return sensor 1 error
Return temperature
sensor (B7) faulty
Burner lockout
(permanent). Lockout
reset required
Check/replace
temperature sensor
40
416
CH return sensor 1 error No further differentiation
Burner lockout
(permanent). Lockout
reset required
Check/replace
temperature sensor
40
417
CH return sensor 1 error No further differentiation
Burner lockout
(permanent). Lockout
reset required
Check/replace
temperature sensor
50
146
DHW 1 temperature
sensor error
Short circuit in DHW
temperature sensor (B3)
Safety shutdown
Check/replace
temperature sensor
50
147
DHW 1 temperature
sensor error
DHW temperature sensor
(B3) faulty
Message
Check/replace
temperature sensor
Содержание TAU 150 UNIT